Choosing Communications
The Video Turnstile Loggers can communicate with the PC over Ethernet, Wi-Fi, RS232 or RS485 links.
Ethernet
Ethernet is appropriate where:
- There is an existing Ethernet infrastructure (cabling and patch panels)
- There is access to the Ethernet infrastructure close to where the VT units will be placed
WiFi
WiFi is appropriate where:
- There is no easily accessible Ethernet cabling
-
Running cables is difficult
- It would cause damage to walls or ceilings or their decoration
- Difficult access from the camera position to a suitable VT unit position
- Installation work time must be minimised
-
The camera must still be mounted at the entrance, but the wLVT unit can be placed
nearby. The Wi-Fi communications can then provide a link either to:
- A PC in the back office
- A wireless access point linking to the existing ethernet cabling
Serial: RS232
Use RS232 when you are using a single logger and the logger will be close (i.e. within about 10 m) to the PC used to collect the data. This is appropriate where there is:
- An LVT with optionally some additional VT units
- A single rack unit with upto 16 VT modules
Serial: RS485
Use RS485 when you have multiple loggers. The RS485 cable can connect to loggers a maximum total distance of 1 km from the PC. So a cable can be run from the PC to loggers distributed around a quite sizable building.
- An RS232-RS485 adapter (type ML800) converts a PC COM port (serial port) from RS232 to RS485.
- A single cable can connect from one ML800 to up to 29 LVT (loggers) in a daisy chain.
- A second COM port can be used to connect to another set of logger units through another RS485 cable.
Next: Choosing the Camera Lens.